Installation of the ceiling-mounted dehumidifier should be divided into two parts:  installation of the dehumidifier and connecting ducts.

Before installation, you need to choose and determine a good installation location from professional  installation perspective first, (if you have decoration drawings, it is best to negotiate with the designer before the installation).

    Technical Parameters

    Model No.

    NBEST-500P

    Nominal dehumidifying (27℃ , 60%RH)

    500PPD

    Input Voltage

    265~277V/ 60Hz

    Rated input power

    2.6 Kw

    Rated input current

    9.5 A

    Air flow

    2800 m³/h

    Applying area (2.6m floor height)

    350-500 ㎡

    Humidity control range

    40%-95%

    Working temperature

    5-38°C

    Net Weight

    130 kgs

    Gross weight

    150 kgs

    Overall dimension

    1300x800x715 mm

    It will be not noticed additionally if any change of above parameters, please contact with us.

    Structure Of Product

    E2DRE}FL5F4A@5C_R(ZIT

    Control Panel

    Y_SHX2B40@__WO{KG4I(_5T
    1.. “On/Off”
    On: press the key into opening mode. Off: press the key into closing mode.
    2.“Humidity Hours +”
    Press the key “set” first then press the humidity value up with 1%RH scale in running mode. Press the
    key “set” first then press hours up with 1 hour scale in timed on/off setting mode.
    During operation, each press will increase the required humidity level by 1%.
    In timer mode, each press will increase the on / off time of the device by 1 hour.
    3.“Humidity Hours-”
    Press the key “set” first then press the humidity value down with 1%RH scale in running mode. Press the key “set” first then press the hours down with 1 hour scale in timed on/off setting mode.
    During operation, each press will decrease the required humidity level by 1%.
    4.“Room RH”
    Current ambient humidity display when in standby mode and running mode. Blinking when at humidity setting mode.
    5.“Set RH” Display when in the humidity setting mode
    6.“Coil ℉ ” Display the temperature of coil
    7.“Room ℉ ” Display the temperature of ambient
    8.“Dehumidifying” Blinking when ompressor is working.
    9.“Water drop icon” Blinking when the fan is working.
    10.“Defrost" Blinking when the machine frosting
    11.“Tankfull” Blinking when tank is full or pull out the tank.
    12.“Timed On / Timed Off” Blinking when in the timed on/off setting mode

    description2